November 27, 2026:


Schneider Electric will double coolant distribution unit manufacturing capacity at its Conselve plant in northern Italy from January 2027 and raise Big Chiller capacity there by 50% by the end of 2026, to supply liquid-cooled AI data centers across Europe. The two numbers describe different bets: a coolant distribution unit (CDU) serves server racks directly, while a chiller rejects heat upstream, and Schneider’s own modeling shows warmer coolant cutting the hours chillers must run.
ITdaily covered the plan on Nov. 25, and The Tech Capital dates Schneider’s announcement to Nov. 24. The English-language wire release followed at 10:51 a.m. ET on Nov. 26.
The release gives percentages only. It names no baseline in units, megawatts or dollars, no investment amount and no job count, so the number of added CDUs and chillers is unknown. For a European operator planning a liquid-cooled hall, the practical question is whether the design needs the added chiller capacity at all.
A CDU separates facility water from the IT cooling loop and pumps a water-glycol mixture to cold plates on GPUs and CPUs. Facility water can carry impurities or minerals, so the separation keeps it away from the cold plates.
Scale explains why the lab’s 5 MW CDU ceiling matters. IN Electronics calculated that transferring 5 MW through water with a 10°C (18°F) temperature rise requires roughly 120 kilograms (265 pounds) of flow every second. That is about 1,900 gallons per minute, using water’s specific heat of 4.18 kilojoules per kilogram per degree Celsius.
Motivair’s own units show the design targets. The MCDU-70, reported Jan. 21, is rated at 2.5 MW and maintains the industry target of 1.5 liters per minute per kW (0.4 gallons per minute per kW), which works out to about 3,750 liters (990 gallons) per minute at full rating. It uses dual heat exchangers and six-unit 4+2 redundancy for large AI facilities. Schneider’s newer WCDU is rated up to 3.5 MW at the same 1.5 liters per minute per kW, or 2.5 MW at 2 liters per minute per kW. The lab’s 5 MW ceiling is roughly 1.4 times the WCDU’s top rating, and the release does not name models for the added Conselve capacity.
Nvidia’s next-generation systems accept coolant up to 45°C (113°F), and co-founder Jensen Huang said at CES that chillers would not be needed, according to Uptime Institute analyst Daniel Bizo. Chiller vendor shares fell as much as 10% afterward. Bizo’s Feb. 3 analysis noted that Nvidia’s GB200 and GB300 systems already support 45°C inlet water, yet most customers still run cooler and keep chillers.
His reasons are mostly engineering. Lower coolant temperatures can help chips sustain higher performance, and a switch to backup generators may cause a temperature drift large enough to trigger throttling. Facilities are expected to stay viable for 20 to 25 years, and cooler coolant adds a margin against cold-plate degradation and debris. Racks run at 45°C would also need entirely dedicated cooling infrastructure, including dry coolers and pumps. Bizo concluded that a chiller-free design is technically feasible but unlikely to suit most operators in the foreseeable future.
Schneider’s modeling adds numbers. Reported Sept. 24 by TechTarget, it covered a 100 MW facility with Nvidia Vera Rubin clusters at rack densities up to 188 kW, in Dallas and Paris. Raising coolant supply from 32°C (90°F) to 45°C (113°F) cut water-usage effectiveness by about 66% in Dallas and 82% in Paris. Chiller assistance started at about 35°C (95°F) outdoors in the optimized 45°C design, versus about 25°C (77°F) at 32°C. The water-saving design can require more dry-cooler capacity and higher capital spending, and power usage effectiveness gains were under 1%. CoolIT said 45°C is the maximum approved temperature for Nvidia warm-water cooling hardware, not necessarily a target.
Climate decides the outcome under those figures. TechTarget reported modeled outdoor temperatures of up to 39°C (102°F) in Dallas and up to 29°C (84°F) in Paris. Dallas’s peaks cross the 35°C (95°F) chiller threshold, while Paris’s peaks stay below it, so chiller assistance would not start at Paris’s modeled peaks in a 45°C design. That comparison is arithmetic on two reported numbers, not a Schneider conclusion, and Uptime’s point stands that most customers keep chillers and prefer cooler setpoints anyway. Schneider’s release does not say what share of the added chiller output is meant for liquid-cooled halls rather than air-cooled sites.
Il Sole 24 Ore reported on May 27 that Schneider CEO Olivier Blum said Italy would become the group’s European center of competence for liquid cooling, with Motivair’s expertise combined into the Italian site. The plant’s cooling products had been air-cooled, and the company was starting to produce liquid cooling systems.
Blum also expects 60% to 70% of new AI-focused data centers built through 2030 to rely on liquid cooling. That is a vendor executive’s projection, not an independent forecast. TrendForce, as cited in TechTimes coverage of LG, estimated liquid cooling was used with 33% of AI chips in 2025 and 53% in 2026.
The expansion builds on Schneider’s purchase of Motivair, the Buffalo, New York liquid-cooling specialist. Schneider signed the agreement on Oct. 16, 2024, and completed the deal on Feb. 28, 2025, taking a 75% controlling interest. Motivair’s announcement put the price at all-cash consideration of $850 million, including a tax step-up, and Schneider expects to buy the remaining 25% in 2028. On Sept. 29, 2025, Schneider said Motivair was expanding production in Italy and India and tripling manufacturing output. That release states no scope, baseline or timeframe for the tripling, so it cannot be tied to Conselve.
Damien Dhellemmes, senior vice president of the Secure Power and Data Center business in Europe, said in the release that AI is changing how customers design and run data centers, which creates strong demand for advanced liquid cooling. He said doubling capacity at Conselve strengthens Schneider’s ability to deliver resilient, scalable and energy-efficient AI infrastructure and brings critical technologies and expertise closer to customers in Europe. The release body adds greater supply-chain resilience as a goal.
Competitors are also adding CDU capacity and ratings. Vertiv said on May 26 that its CoolChip CDU 2300, a 2.3 MW liquid-to-liquid unit, is now offered in Europe, the Middle East and Africa. Its release does not say where the unit is built.
LG’s 2.6 MW CDU has qualified as an Nvidia DSX Ready unit, the largest capacity in that program as TechTimes reported on Oct. 5. Samsung plans a CDU factory in Gwangju, South Korea, with full operations expected in early 2028. Ratings depend on flow rate, so these figures are not directly comparable. Schneider’s expansion also arrives during a consolidation wave that includes Eaton’s completed acquisition of Boyd Thermal and Ecolab’s completed acquisition of CoolIT Systems, priced at about $4.75 billion.
The MCDU-70 can be ordered through Schneider’s manufacturing hubs in North America, Europe and Asia, and Schneider says its CDU portfolio now runs from 105 kW to 3.5 MW. Producing in Europe is the closer-to-customers argument Schneider makes in its release.
Several gaps remain. The release gives +100% for CDUs and +50% for chillers without a baseline. It says Schneider is investing in the lab but names no amount, and it does not say how many jobs the expansion creates.
The chiller timing is also loose. “By the end of 2026” leaves open whether the increase is already in place, and IN Electronics says the first manufacturing increases take effect “over the coming months.” No customer, order or backlog figures accompany the announcement.
Reliability is the reason test capacity matters. Schneider’s David McGlocklin wrote on July 15 that liquid cooling failures typically trace to pump failures, fouled heat exchangers, coolant degradation, leaks and sensor faults, and that high-density AI systems without backup can reach critical temperatures in seconds.
For a European operator, Conselve signals more regionally built CDU and chiller supply starting in January 2027 and a larger test lab in December 2027. Schneider has not published baselines, investment or models, and its own 45°C modeling shows that the coolant setpoint and local climate, not only rack power, decide how much chiller capacity a hall needs.
A CDU separates facility water from the IT cooling loop and pumps a water-glycol mixture to cold plates on GPUs and CPUs. Facility water can carry impurities or minerals, so keeping the loops apart protects the chips’ cold plates. Schneider’s CDU portfolio spans 105 kW to 3.5 MW per unit.
Most will keep them for now, and climate matters. Uptime Institute says most Nvidia customers still run cooler coolant and keep chillers. Schneider’s modeling has chillers assisting above 35°C (95°F) outdoors in an optimized 45°C design, a threshold that Dallas’s modeled 39°C (102°F) peaks cross and Paris’s 29°C (84°F) peaks do not. Nvidia’s Ali Heydari, director of data center cooling and infrastructure, has said chillers might be needed for about 1% of the year in some climates, and TechTimes noted that share could be considerably higher where ambient temperatures approach 45°C.
Heat builds fast, so designs add redundancy. Schneider’s McGlocklin recommends CDUs with onboard sensors and pump redundancy, plus thermal storage tanks on both the server loop and the facility water loop. In most failures, he wrote, redundant pumps, sensors or units take over the load.